[Illustration: FIG. 2,217.--Horn break switch. ~In operation~, the arc formed at break, will travel toward the extremities of the horns because of the fact that a circuit will tend to move so as to embrace the largest possible number of lines of force set up by it. Hence, the arc that starts between the horns where they are near together rises between them until it becomes so attenuated that it is extinguished.]

[Illustration: FIG. 2,218.--Westinghouse rear connected motor starting switch, for pressures up to 600 volts. It is used for starting rotary converters and direct current motors of large capacity having starting torque small enough to permit cutting out the starting resistance in few steps. The clips can be connected to any type of resistor, the steps of which are successively short circuited as the switch closes; the amount of resistance in the armature circuit is thus gradually reduced. A pause should be made after each step of resistance is thrown in to allow the motor speed to accelerate. If the starting switch do not have to carry the full load current and can be short circuited by another switch, a starting switch of smaller capacity equivalent to 50 per cent of running current of the machine can be used. The switch is of the single pole, single throw, rear connected, four point, knife blade type.]

Hawkins Electrical Guide v. 7 (of 10) — Part 35

Ans. The moving arm of the switch draws the fuse through the tube, thus opening the circuit without much disturbance.

Hawkins Electrical Guide v. 7 (of 10) — Part 35

[Illustration: FIG. 2,219.--Baum disconnecting switch with horns and auxiliary contacts (Pacific Mfg. Co.). This switch is for use on systems operating at 100,000 volts or over. It has a spacing of five feet between outer insulators, is equipped with auxiliary shoes that break the circuit between the horns, diverting it from the current carrying contacts so that they are not attacked by the arc.]

Hawkins Electrical Guide v. 7 (of 10) — Part 35

~Ques. What is the objection to the metal fuse switch?~

Ans. The powder is set flying by the explosion of the arc, which, as it settles, gets into the bearings of any machine that may be in the vicinity.

Ans. One provided with horn shaped extensions to the contacts, as shown in fig. 2,219.

The arc formed on breaking the circuit, as it travels toward the extremities of the horns, becomes attenuated and is finally ruptured.