Lightning protection devices, or lightning _arresters_, are devices for providing a path by which lightning disturbances or other static discharges may pass to the earth.
Lightning arresters, designed for the protection of transmission lines, must perform this function with a minimum impairment of the insulation of the lines.
In general the construction of lightning arresters comprise
1. Air gaps; 2. Resistances; 3. Inductances; 4. Arc suppressing devices.
~Ques. What are the causes of static charges?~
Ans. They may be caused by sandstorms in dry climates, or may be due to grounds on the high pressure side of a system.
~Ques. What causes high frequency oscillations?~
Ans. They are usually due to lightning discharges in the vicinity of the line.
~Ques. What are the requirements of lightning protection devices?~
Ans. They must prevent excessive pressure differences between line and ground, line and line, and between conductor turns in the electrical apparatus.
~Air Gap Arresters.~--method of relieving any abnormal pressure condition is to connect a discharge air gap between some point on an electric conductor and the ground. The resistance thus interposed between the ground and the conductor is such that any voltage very much in excess of the maximum normal will cause a discharge to ground, whereas at other times the conductor is ungrounded because of the air gap. This forms the principle of air gap arresters.
[Illustration: FIG. 2,349.--Non-arcing multi-gap arrester. Based on the principle of employing for the terminals across which the arc is formed, such metals as are least capable of maintaining an alternating arc between them. This so called non-arcing property of certain metals was discovered by Alexander Wurtz. The action is such that the "line current" which follows the lightning discharge follows as an arc, but is stopped at the end of one alternation because of the property of the non-arcing metals to carry an arc in one direction, but requiring an extremely high voltage to start a reverse arc. The non-arcing metals ordinarily employed are alloys of zinc and copper. Plain multi-gap arresters as here shown operate satisfactorily with the smaller machines and on circuits of limited power, but for large machines of close regulation, and therefore of very large momentary overload capacity, especially when a number of such are operated in parallel, such arresters were found insufficient, the line current following the lightning discharge frequently was so enormous that the circuit did not open at the end of the half wave, that is the arrester held the arc and was destroyed. The introduction of synchronous motors made it necessary that the arc should be extinguished immediately, otherwise the synchronous motors and converters would drop out of step, and the system would in this way be shut down. To insure the breaking of the arc, resistance was introduced in the arrester, the modified device being known as the low equivalent arrester as shown in fig. 2,350.]