CEAR namely Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2010 are regulations framed by Central Electricity Authority of India under Indian Electricity Act, 2003, to regulate measures relating to safety and electric supply in India.

History

CEAR came into effect 20 September 2010, in place of The Indian Electricity Rules, 1956.

Central Electricity Authority Regulations

The Electricity Act, 2003, was formulated combining the Indian Electricity Act 1910 and Indian Electricity (supply) Act 1948.

Central Electricity Authority Regulations

Earthing provisions and safety

Under CEAR, rule 41, there is specific provision of earthing neutral wire of a 3-phase, 4-wire system and the additional third wire of a 2- phase, 3-wire system. Earthing is to be done with two separate connections. Grounding system also to have minimum two or more earth pits (electrode) such that proper grounding takes place. As per the rule 42, installation with load above 5 kW exceeding 250 V shall have suitable Earth leakage protective device to isolate the load in case of earth fault or leakage.

Central Electricity Authority Regulations

Neutral and earth run separately on overhead line/cables. Separate conductor for overhead lines and armouring of cables are used for earth connection. Additional earth electrodes/pits are installed at user ends for proper earth.

All metal casing or metallic coverings of electric supply line or apparatus to be connected with earth and all such earthling points shall be so joined to make good mechanical and electrical connection in complete system.

Earthing in mines

Earthing in an underground mine shall be carried out by connection to an earthing system at the surface of the mine as per rule 99.

As per rule 100, protective equipment is to be placed in the mines for automatic disconnection of supply when there is earth fault exceeding 750 milliampere in 250 V to 1000 Volt installations. For open cast mine the limit is 50 ampere in installations of voltage exceeding 1100 V and up to 11 kV. The earth leakage current is to be restricted by placing suitable neutral grounding resistance (NGR) in all the distribution transformers.

Salient features

Chapters and regulations there in:-

Chapter - I Definitions

1 Short title and Commencement

2 Definitions

Chapter - II

3 Designating person(s) to operate and carry out the work on electrical lines and apparatus

4 Inspection of designated officers and other safety measures

5 Electrical Safety Officer

6 Safety measures for operation and maintenance of electric plants

7 Safety measures for operation and maintenance of transmission, distribution systems

8 Keeping of records and inspection there of

9 Deposit of maps

10 Deposit of printed copies

11 Plan for area of supply to be made and kept open for inspection

Chapter - III General safety requirements

12 General safety requirements, pertaining to construction, installation, protection, operation and maintenance of electric supply lines apparatus

13 Service lines and apparatus on consumer’s premises

14 Switchgear on consumer’s premises

15 Identification of earthed and earthed neutral conductors and position of switches and switchgear therein

16 Earthed terminal on consumer’s premises

17 Accessibility of bare conductors

18 Danger Notices

19 Handling of electric supply lines and apparatus

20 Supply to vehicles and cranes

21 Cables for portable or transportable apparatus

22 Cables protected by bituminous materials

23 Street boxes

24 Distinction of different circuits

25 Distinction of the installations having more than one feed

26 Accidental charging

27 Provisions applicable to protective equipment

28 Display of instructions for resuscitation of persons suffering from electric shock

29 Precautions to be adopted by consumers, owners, occupiers, electrical contractors, electrical workmen and suppliers

30 Periodical inspection and-testing of Installations

31 Testing of consumer's installation

32 Installation and testing of generating units

Chapter - IV General conditions relating to supply and use of electricity

33 Precautions against leakage before connection

34 Leakage on consumer's premises

35 Supply and use of electricity

36 Provisions for supply and use of electricity in multi-storied building more than 15 meters in height